Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T04CM05400
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2005 | Jim Egan | FIRE | REVIEW | Denied | Fire sprinklers required. |
| 01/12/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the insulation for exterior ducts (A4/M0.1) to comply with Section 503.3.3.3, IECC 2000. 2. Show that adequate clearance for maintenance and replacement of the fan coil unit is present. Reference Sections 306.1 and 306.3, IMC 2000, and the manufacturer's service requirements. 3. Show the size, route, and termination of the secondary drain from the fan coil unit. Reference Section 307.2.3, IMC 2000. 4. Provide calculations to show that the specified heat pump system is capable of maintaining the space temperature at 68F degrees on a design day (32F degrees) without auxiliary heat. Reference Section 309, IMC 2000. |
| 01/27/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See comments posted with T04CM05387. |
| 02/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 2/15/05 ACTIVITY NUMBER: T04CM05387, T04CM05400, T04CM05401 PROJECT NAME: PROJECT ADDRESS: 534 Herbert Ave, 537 S. 5th Ave. #1, 537 S. 5th Ave. #2 ARCHITECT / ENGINEER: Rick Bright PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Lots are now combined therefore code analysis needs to be provided for the buildings on one lot. Justify existing construction is adequate. 2) Address for the laundry building? 3) Clarify occupancy use for each building. It appears to have a C of O as a adult care facility but no permits have been pulled clarifying use of each room. Clarify use of each room. If commercial use? Plans need to be submitted as a commercial building, therefore structural calculations will need to be provided. 4) R-4 15 occupant Adult care requires fire sprinklers for the facilities. 5) Bldg. 535 S. 5th Ave has a open violation which needs to be resolved to issue any new permits on this lot. 6) Clarify accessibility per Chapter 11 of the IBC. 7) Clarify per Chapter 34, section 3409 accessibility for existing buildings. 8) Conflict repair concrete slab only or adding new porches per section A5/A2.2? 9) Detail B1/A5.1 how are you placing anchor bolt in existing masonry wall? |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 02/16/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |