Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM05387
Parcel: 117070860

Address:
534 S HERBERT AV

Review Status: Stopped

Review Details: RESUBMITTAL

Permit Number - T04CM05387
Review Name: RESUBMITTAL
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2005 JIM EGAN FIRE REVIEW Denied Fire sprinklers required per 203 IBC Sec. 903.2.7.
07/29/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the violations noted on activity T01VL02730 are being addressed.
07/29/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the violations noted on activity T01VL02730 are being addressed.
07/29/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 7/29/05
ACTIVITY NUMBER: T04CM05387, T04CM05400, T04CM05401
PROJECT NAME:
PROJECT ADDRESS: 534 Herbert Ave, 537 S. 5th Ave. #1, 537 S. 5th Ave. #2
ARCHITECT / ENGINEER: Rick Bright
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify occupancy use for each building. It appears to have a C of O as a adult care facility but no permits have been pulled clarifying use of each room. Clarify use of each room. If commercial use? Plans need to be submitted as a commercial building, therefore structural calculations will need to be provided. It appears you want to change occupancy to a R2, therefore justification needs to be provided per the IBC 2003.

2) All buildings have a open violation which needs to be resolved to issue any new permits on this lot. See copy of violation T01VL02730.
3) Clarify accessibility per Chapter 11 of the IBC.
4) Clarify per Chapter 34, section 3409 accessibility for existing buildings.
08/01/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Address violation T01VL02730.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2005 ANGIE SHOFFSTALL REJECT SHELF Stop
07/14/2005 ANY OUT TO CUSTOMER Stopped