Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
01/19/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
12/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste and vent riser diagram to coordinate with the floor plan. Show the trap on P3H. 2. Show how the water pipes were sized. |
12/14/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
12/14/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/14/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
12/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the relocated exhaust fan is to be installed. 2. Show how adequate ventilation is being provided to the new dining room. |
12/22/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/19/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |