Permit Number: T04CM05379
Parcel: 13818025A

Address:
7146 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM05379
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2005 Gerry Koziol WWM REVIEW Denied need wastewater 5th floor Par /Non Par evaluation
02/02/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM05379 2nd REVIEW

2/03/05 7146 S. 6th AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED.

FLOOR PLANS:

1. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R307.2

2. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE. SEER602.10 .

3. DIMENSION THE OPENING THROUGH BEDROOM #4 IN THE EXISTING WALL. THE SCALED DIMENSION IS 9'-3", IS IT ACCURATE?

STRUCTURAL PLANS:

1. PROVIDE THE EXISTING ROOF FRAMING PLAN WITH DIMENSIONS.

2. CROSS SECTION / 1 ; HOW DOES THE ½" GYP BOARD ON THE CEILING COMPLY WITH TABLE R702.3.5 FOOTNOTE D?

3. SPECIFY LUMBER GRADE AND SPECIES.

SECTIONS - DETAILS - MISC. NOTES:

1. ARE SECTION NOTES 8 AND 8 AND 11 TRANSPOSED?

2. 5 / 2 ; THE NAILING TABLE SHOULD REFER TO TABLE R602.3(1).




PLUMBING PLANS:

1. JUSTIFY THE EXISTING WATER DISTRIBUTION SYSTEM'S ABILITY TO SERVE THE EXISTING AND THE PROPOSED FIXTURES. ANY HOSE BIBS?

2. INDICATE THE BTU RATING OF THE ELECTRIC WALL HEATERS AND THEIR LOCATION. HEATERS ARE REQUIRED TO BE PERMANENTLY INSTALLED.

3. PROVIDE BOTH COMBUSTION AND RELIEF AIR FOR THE WATER HEATER. SEE THE STATE PLUMBING CODE'S TABLE 5-A .

MECHANICAL PLANS:

1. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.8.

ELECTRICAL PLANS:

1. WHAT PART OF THE ELECTRICAL SERVICE IS ON THE ROOF?

2. THE LAUNDRY CIRCUIT IS REQUIRED TO BE DEDICATED TO THE LAUNDRY ALONE. SEE E3603.3 .

3. PROVIDE SMOKE DETECTORS IN THE AREAS IMMEDIATELY OUTSIDE THE SLEEPING ROOMS. SEE E313.1 .

MODEL ENERGY CODE:

1. HOW DOES R-30 INSULATION FIT IN 2X8 RAFTERS?

2. HOW DOES R-19 INSULATION FIT IN 2X4 STUDS?

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2005 TAMI ACHONG OUT TO CUSTOMER Completed
02/04/2005 SUE REEVES REJECT SHELF Completed