Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM05370
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide specifications and operating parameters for the water heater. The model noted on sheet A1 is not offered by the manufacturer in sizes greater than 50 gallons. Clarify the electrical requirements with regard to the heating elements. 2. Add shut off valve for the water heater. See marked up drawing. 3. Confirm the water pressure calculations and correct the demand calculations. See the revised water fixture units on the drawing. |
| 02/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/23/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/24/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/24/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |