Permit Number: T04CM05370
Parcel: 133243720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM05370
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications and operating parameters for the water heater. The model noted on sheet A1 is not offered by the manufacturer in sizes greater than 50 gallons. Clarify the electrical requirements with regard to the heating elements.
2. Add shut off valve for the water heater. See marked up drawing.
3. Confirm the water pressure calculations and correct the demand calculations. See the revised water fixture units on the drawing.
02/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/23/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/24/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2005 TAMI ACHONG OUT TO CUSTOMER Completed