Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05370
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the water demand calculation using the fixture unit values from Table 6-3, UPC 1994. 2. Comment not addressed. Provide calculations to show how the water piping has been sized. Reference Section 610.4, UPC 1994. 3. Comment not addressed. Provide riser diagrams for water and waste & vent piping. 4. Comment not addressed. Provide specifications and operating parameters for the water heater. 5. Comment not addressed. Provide information to show that the owner furnished fixtures will meet the requirements of Section 301.1, UPC 1994. 6. Comment not addressed. Provide specifications for the grease trap. Reference Section 1011.0,UPC 1994. 7. Comment not addressed. Provide calculations to show how the natural gas piping has been sized. Show all connected gas loads and the developed pipe length. Reference Section 1217.1, UPC 1994. |
| 01/03/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Show how the hood is to be supported from the structure and provide structural calculations. Reference Section 507.6, IMC 2000. 2. Comment not addressed. Show how the proposed hood complies with the requirements of Sections 507.2.1 and 507.13, IMC 2000. 3. Comment not addressed. Provide make-up air for the hood. Reference Section 508, IMC 2000. 4. Comment not addressed. Show the size and location of the hood on the drawing. 5. Comment not addressed. Provide calculations showing that the facility has adequate ventilation. Reference Section 403.3, IMC 2000. |
| 01/03/2005 | Gerry Koziol | WWM | REVIEW | Denied | recounted all plumbing fixtures-need wastewater 8th floor credit evaluation. need to re-review after cot & health dept |
| 01/19/2005 | Robert Suba | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.provide panel location on electric plan. 2.install disconnect at water heater. 3.provide wiring schematic for hood-make up air interlock and provide fresh air equipment. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/19/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 01/19/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |