Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM05352
Parcel: 12405051A

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM05352
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
01/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t04cm05352 denied 12/10/04
1. Please check the fusing on the 1 HP Mastercool. It should draw 16 A at 120 V, and the overload may be oversized. If this was sized per manufacturer's recommendations, it should be OK.
2. Interlock diagram indicates that EF-1 and SF-1 are on Panel A. No such single phas loads on Panel A. Add them, and clarify new from existing loads.
3. Total amps on Panel A appear to exceed this panel's rating. Please clarify, document existing loads, and add new loads.
4. Provide existing load on Panel B.
01/19/2005 CAGUILA1 FIRE REVIEW Needs Review
12/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the proposed hood meets the requirements of Section 507, IMC 2000.
2. Provide an smooth, cleanable, non-absorbent surface covering for the wall behind the hood. Reference Section 507.9, IMC 2000.
3. Revise the exhaust fan air flow to comply with Section 507.13, IMC 2000.
4. Clarify the balancing information for the make-up air unit. Reference Section 508, IMC 2000.
5. Show the work platform for the exhaust fan.
6. Show the method for supporting the make-up air unit.
12/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the gas load requirements for the double oven.
2. Resize the gas piping using Table 12-3, UPC 1994.