Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM05352
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t04cm05352 denied 12/10/04 1. Please check the fusing on the 1 HP Mastercool. It should draw 16 A at 120 V, and the overload may be oversized. If this was sized per manufacturer's recommendations, it should be OK. 2. Interlock diagram indicates that EF-1 and SF-1 are on Panel A. No such single phas loads on Panel A. Add them, and clarify new from existing loads. 3. Total amps on Panel A appear to exceed this panel's rating. Please clarify, document existing loads, and add new loads. 4. Provide existing load on Panel B. |
| 01/19/2005 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 12/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the proposed hood meets the requirements of Section 507, IMC 2000. 2. Provide an smooth, cleanable, non-absorbent surface covering for the wall behind the hood. Reference Section 507.9, IMC 2000. 3. Revise the exhaust fan air flow to comply with Section 507.13, IMC 2000. 4. Clarify the balancing information for the make-up air unit. Reference Section 508, IMC 2000. 5. Show the work platform for the exhaust fan. 6. Show the method for supporting the make-up air unit. |
| 12/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the gas load requirements for the double oven. 2. Resize the gas piping using Table 12-3, UPC 1994. |