Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM05330
Parcel: 12809005E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM05330
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/05/2005 ROBERT SHERRY WATER REVIEW Approved
04/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/11/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/18/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/20/05
ACTIVITY NUMBER: T04CM05330 & T04CM05559
PROJECT NAME: Exercise Room & Addition Business Office
PROJECT ADDRESS: 5353 E 22 ND St. #101
ARCHITECT / ENGINEER: Antonio Romano
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Separated use 2 hour separation between B and R2 use. Please clarify / locate and provide wall section / ceiling section. Clarify how you are achieving 2 hr. Justify per UL (underwriting laboratories) listing.
2) Detail connection of beam 5 1/8" x 12" GLM beam at existing wall. Clarify bearing of Glulam beam to carry load to footing. Column?
04/29/2005 PETER MCLAUGHLIN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2005 KMEDINA1 OUT TO CUSTOMER Completed