Permit Number: T04CM05330
Parcel: 12809005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05330
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 JIM EGAN FIRE REVIEW Approved
02/07/2005 ROBERT SHERRY WATER REVIEW Approved
02/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show any modifications that have been made to the mechanical systems.
2. Provide calculations to show that the ventilation for the space conforms to Section 401, IMC 2000.
02/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a plumbing plan to show all of the revisions that have been made to the plumbing system. Reference Section 103.2.3, UPC 1994.
02/14/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
02/23/2005 GERRY KOZIOL WWM REVIEW Passed
03/03/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 3/1/05
ACTIVITY NUMBER: T04CM05330 & T04CM05559
PROJECT NAME: Exercise Room & Addition Business Office
PROJECT ADDRESS: 5353 E 22 ND St. #101
ARCHITECT / ENGINEER: Antonio Romano
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Need to have a complete site plan showing all buildings. Locate on site the building that is being remodeled. Dimensions from other buildings. Justify per section 302.3.2.
2) Separated use 2 hour separation between B and R2 use. Please clarify / locate and provide wall section.
3) Exercise room A-3 use? See section 302.2.1. Please clarify / justify.
4) Separated use see table 302.3.2, 2 hr. fire separation required between a B use and R2/A3. Please clarify / justify.
5) Detail connection of beam 5 1/8" x 12" GLM beam at existing wall.
6) Clarify exercise room 1 story or 2 story structure. Provide calculations accordingly. Beams carrying roof and flooring load?
7) Clarify existing roof framing direction of spans by rafters / floor joists. Existing office and exercise room.
8) Clarify location of shear walls and detail on drawings..
9) Clarify accessibility Chapter 11 accessible route section 1104.
10) Justify / clarify per section 903.2.7 & 907.2.10.1.2.
11) Structural Engineer need to review and stamp sht. 4/4.
03/10/2005 PETER MCLAUGHLIN ZONING REVIEW Denied The approved site plan shows a pedestrian sidewalk connecting to the sidewalk located within the existing right-of-way along 22nd Street. This ped. connection is required and the 5-foot pedestrian refuge shown on the partial site plan must also include a 4-foot sidewalk. Revise plan to show accessible pedestrian route between the new addition and the PAAL. Also, for reference, show the parking spaces as they exist within the vehicle use area shown on the partial site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2005 TAMI ACHONG OUT TO CUSTOMER Completed