Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM05310
Parcel: 11005549B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM05310
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05310 DENIED 12/15/04
1. WH-1 and WH-2 are listed as 3 KW on Sheet P1. Electrical panel schedule lists 2500 VA. Coordinate with Plumbing and clarify. If WHs change to 3 KW on electrical, please note that overcurrent protection should be re-checked and load calculations revised.
12/22/2004 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2004 LISA LESNY OUT TO CUSTOMER Completed