Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM05310
Parcel: 11005549B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05310
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
12/07/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
12/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05310 DENIED 12/08/04
1. Minimum font size is 10 point, which is a little over 1/8".
2. WH-1 and WH-2 are listed in Plumbing Drawings, but are not powered on Electrical. Pls coordinate & clarify. Plans Examiner will check feeder loading after this comment is addressed.
3. Please check loading on Lighting Circuits 2 and 4, and the AC circuits. My figures are a bit higher.
12/08/2004 ROBERT SHERRY WATER REVIEW Approved
12/08/2004 JIM EGAN FIRE REVIEW Approved
12/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/10/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Firewall is not located according to shall plan location, therefore adequate fire seperation is not provided.
12/14/2004 GERRY KOZIOL WWM REVIEW Approved