Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05310
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 12/07/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/08/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM05310 DENIED 12/08/04 1. Minimum font size is 10 point, which is a little over 1/8". 2. WH-1 and WH-2 are listed in Plumbing Drawings, but are not powered on Electrical. Pls coordinate & clarify. Plans Examiner will check feeder loading after this comment is addressed. 3. Please check loading on Lighting Circuits 2 and 4, and the AC circuits. My figures are a bit higher. |
| 12/08/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/08/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/08/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/10/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Firewall is not located according to shall plan location, therefore adequate fire seperation is not provided. |
| 12/14/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |