01/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05305 DENIED 1/20/05
1. Please clarify track lighting branch circuit(s). These lights appear to be all on B-17 (65 total LF) (75 per NEC 220.12 B) = 4875 VA, which computes to over 40 A. Please reconfigure as necessary, then add for continuous load.
2.
01/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved