Review Details: COMMERCIAL TI

Permit Number - T04CM05305
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2004 JIM TATE ENGINEERING REVIEW Approved
12/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water calculation to limit the water velocity to 8 fps. Revise pipe sizes as required.
2. Revise the fixture unit calculations, using the public value for the clothes washer. Revise pipe sizes as required.
3. Provide listings for the fixtures or specify the qualifications of the proposed fixtures.
12/07/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/07/2004 ROBERT SHERRY WATER REVIEW Approved
12/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05305 DENIED 12/07/04
1. New WH is 240V, 2.5 KW on Sheet P1.1, but is 208V, 4500KW on Panel Schedule. Please coordinate with Mechanical and clarify.
2. Provide conductor size for Circuit B-2,4.
12/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations using the values from Table 403.3, IMC 2000.
12/09/2004 CAGUILA1 ZONING REVIEW Needs Review
12/09/2004 CAGUILA1 WWM REVIEW Needs Review
12/09/2004 CAGUILA1 FIRE REVIEW Needs Review