| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 12/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water calculation to limit the water velocity to 8 fps. Revise pipe sizes as required. 2. Revise the fixture unit calculations, using the public value for the clothes washer. Revise pipe sizes as required. 3. Provide listings for the fixtures or specify the qualifications of the proposed fixtures. |
| 12/07/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM05305 DENIED 12/07/04 1. New WH is 240V, 2.5 KW on Sheet P1.1, but is 208V, 4500KW on Panel Schedule. Please coordinate with Mechanical and clarify. 2. Provide conductor size for Circuit B-2,4. |
| 12/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations using the values from Table 403.3, IMC 2000. |
| 12/09/2004 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 12/09/2004 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 12/09/2004 | CAGUILA1 | FIRE | REVIEW | Needs Review |