| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 4/26/0 ACTIVITY NUMBER: T05CM05298 PROJECT NAME: RESIDENTIAL STAIRS PROJECT ADDRESS: 1030 N. 4TH AVE ARCHITECT / ENGINEER: GEORGE STEVENSON PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) MINIMUM TREAD DEPTH PER IRC 2003 SHALL BE 10 INCHES. IT APPEARS PER DETAIL #3 E1 BY STEELCON TREAD DEPTH EQUALS 9". 2) RISER HEIGHT? IRC R311.5.3.1. 3) OPEN RISERS ARE PERMITTED, PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT PERMIT THE PASSAGE OF A 4" DIAMETER. 4) PER IRC 2003 PROVIDE STAIRWAY ILLUMINATION PER R303.6 & R303.6.1 LIGHT ACTIVATION. 5) PROVIDE SPECIAL INSPECTION FOR EPOXY ANCHORS. 6) CLARIFY JUSTIFY LANDING & DOOR SILL HEIGHT PER R311.4.3 LANDINGS AT DOOR. PLEASE PROVIDE DIMENSIONS. 7) ORIGINAL FIELD WELDING SPECIAL INSPECTION FORM NEEDS TO BE PROVIDED BEFORE PERMIT CAN BE ISSUED. 8) DIMENSION HEADROOM UNDER STAIRWAY FOR EXIT DOOR, SEE R311.5.2. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/02/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |