Permit Number: T04CM05292
Parcel: Unknown

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T04CM05292
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2005 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
01/19/2005 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1-20-05
ACTIVITY NUMBER: T04CM05292
PROJECT NAME: Cell Tower
PROJECT ADDRESS: 2553 S. Pantano Rd.
ARCHITECT / ENGINEER: Young Design Corp.
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide structural calculations for retaining wall.
2) Retaining wall detail needs to provide proper drainage and weep holes.
3) Approval letter from TEP stating its o.k. to mount antennas on their pole.
02/02/2005 JAY HOGAN OPERATIONS REVIEW Approved
12/08/2004 GLENN MOYER PLANNING-CITY HALL REVIEW Denied Condition e. requires antennas to be flush mounted to the pole. The antenna configuration detail on sheet RF-1 shows mounting arms.
12/08/2004 Jim Egan FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2005 DELMA ROBEY OUT TO CUSTOMER Completed