Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM05260
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/06/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the plumbing fixture schedule using water and waste fixture units as shown in Tables 6-3 and 7-3, UPC 1994. 2. Show how the water piping has been sized. Reference Section 610.4, UPC 1994. 3. Provide a riser diagram for the water piping. 4. A prep sink must be indirectly wasted. Reference Sections 801.2 and 803.0, UPC 1994. 5. Provide a grease trap for the 3-compartment sink. Reference Sectionws 1011.1, 1011.3, and 1011.4, UPC 1994. 6. Show the location and size of the water meter and reduced pressure backflow preventer. 7. Revise the sizes of the waste piping per Table 7-5, UPC 1994. |
12/06/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/06/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the project area has adequate ventilation. Reference Section 403.3, IMC 2000. |
12/06/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/15/2004 | TACHONG1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/15/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |