Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM05260
Parcel: 12601003C

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM05260
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing fixture schedule using water and waste fixture units as shown in Tables 6-3 and 7-3, UPC 1994.
2. Show how the water piping has been sized. Reference Section 610.4, UPC 1994.
3. Provide a riser diagram for the water piping.
4. A prep sink must be indirectly wasted. Reference Sections 801.2 and 803.0, UPC 1994.
5. Provide a grease trap for the 3-compartment sink. Reference Sectionws 1011.1, 1011.3, and 1011.4, UPC 1994.
6. Show the location and size of the water meter and reduced pressure backflow preventer.
7. Revise the sizes of the waste piping per Table 7-5, UPC 1994.
12/06/2004 ROBERT SHERRY WATER REVIEW Approved
12/06/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the project area has adequate ventilation. Reference Section 403.3, IMC 2000.
12/06/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/15/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed