Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS
1) Provide a site plan , not a photograph, showing clearly the location of the tower.
The photo. shown is not clear, the 540' is from where to ? The N-S dimenson
Is 50' or 75'? Clarify!
2) Provide lateral design as per the 2003 IBC.
3) Provide engineering calc`s for footing or caisson design.

3/15/05

1) Comply to comments 2 and 3 above.
03/21/2005 GLENN MOYER PLANNING-CITY HALL REVIEW Denied 1. Show antenna plan view layout for both sets of antennas in compliance with condition d. Only Cricket has been added to the plans, ATT has not.
03/28/2005 DROBEY1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2005 DELMA ROBEY OUT TO CUSTOMER Completed