Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05246
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2005 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 12/16/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | T04CM05246 .. DGL .. 12/3/04 (REVISED 12/16/04) 1. PROVIDE COMPLETED AND SIGNED AND DATED CODE REVIEW CHECKLIST. 2. FULLY DIMENSION AND DETAIL ACCESSIBLE TOILET ROOM, PER 2003 ANSI A117.1 : PROVIDE AND LOCATE VERTICAL GRAB BAR, DIMENSION TOILET PAPER DISPENSER IN FRONT OF WATER CLOSET 7-9", INDICATE INSULATION ON PIPING UNDER LAVATORY. 3. PROVIDE DETAILS FOR CONNECTION TO EXISTING STRUCTURE ABOVE, TYPICAL. 4. PROVIDE PROJECT VALUE. 5. SHOW HOW STOREFRONT IS SUPPORTTED STRUCTURALLY. |
| 12/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the vent piping to comply with Section 901.0, UPC 1994. Second request. 2. Coordinate the riser diagram for the water piping with detail B/P-2. Explain the nature of the 9 items supplied with CW (located near restroom). 3. Provide manufacturer's listing information to justify the lack of backflow preventers for each foot spa. (see handout for foot spas). Reference Section 603.0, UPC 1994. 4. Provide a cleanout for P-4. Reference Section 707.4, UPC 1994. 5. The T&P for the water heater may not terminate over a laundry sink due to the potential for scalding. Reference Section 608.5, UPC 1994. 7. Show how the chart for sizing of the water pipes agrees with the provided calculations. Reference Section A4, UPC 1994. |
| 12/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM05246 DENIED 12/16/04 1. Sheet E1, with Electrical Specifications, is missing. 2. Plans shall be sealed by a Registrant in the State of Arizona. |
| 12/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listing information for the energy recovery ventilator. 2. Show where the ducts connected to the energy recovery ventilator terminate in relation to the nail salon and the mall. 3. Show where the condensing unit is located in relation to the nail salon and the mall. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/21/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |