Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM05246
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05246
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
12/02/2004 DAVID RIVERA ZONING REVIEW Approved
12/03/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the vent piping to comply with Section 901.0, UPC 1994.
2. Provide a riser diagram for th water piping.
3. Provide reduced pressure backflow preventers for both hot and cold water for each foot spa. (see handout for foot spas). Reference Section 603.0, UPC 1994.
4. Revise the fixture units shown for the mop sink. Reference TAble 6-3, UPC 1994.
5. Provide an upper terminal cleanout for the waste line for the foot spas. Reference Section 707.4, UPC 1994.
6. Show the size, route, and termination of the T&P for the water heater. Note: termination in a laundry tub. Reference Section 608.5, UPC 1994.
7. Show how the water piping has been sized. Reference Section 610.4, UPC 1994.
12/03/2004 ANY BUILDING-COMMERCIAL REVIEW Denied T04CM05246 .. DGL .. 12/3/04

1. PROVIDE COMPLETED AND SIGNED AND DATED CODE REVIEW CHECKLIST.
2. PROVIDE LOCATION PLAN LOCATING TENANT SPACE IN MALL.
3. FULLY DIMENSION AND DETAIL ACCESSIBLE TOILET ROOM.
4. CALLOUT CEILING SUSPENSION SYSTEM TO BE USED ON PROJECT.
5. PROVIDE DETAILS FOR CONNECTION TO EXISTING STRUCTURE ABOVE, TYPICAL.
6. PROVIDE PROJECT VALUE.
12/03/2004 ROBERT SHERRY WATER REVIEW Approved
12/03/2004 JIM EGAN FIRE REVIEW Approved
12/03/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the termination of the condensate drain with the plumbing design.
2. Provide calculations to show that the ventilation for the project complies with Section 403.3, IMC 2000.
3. The minimum exhaust for a restroom is 75 cfm per water closet or urinal. Refernce Table 403.3, IMC 2000.
4. Provide duct insulation with a minimum thermal resistance of R-5. Reference Section 803.2.8, IECC 2000.
12/03/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/16/2004 EGRANT1 WWM REVIEW Needs Review