Permit Number: T04CM05219
Parcel: 13317062A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05219
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/30/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
12/01/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/01/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
12/01/2004 ROBERT SHERRY WATER REVIEW Approved
12/01/2004 JIM EGAN FIRE REVIEW Approved
12/01/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the restrooms have adequate ventilation. Reference Section 403.3, IMC 2000.
2. Revise the ventilation calculations using the appropriate room types as shown in Table 403.3, IMC 2000.
3. Confirm the final amount of outside airflow for each fan coil and AC-5 using the procedure shown in Section 403.3.2, IMC 2000.
12/01/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/08/2004 EGRANT1 WWM REVIEW Needs Review