Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05219
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 11/30/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/01/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/01/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/01/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/01/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/01/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the restrooms have adequate ventilation. Reference Section 403.3, IMC 2000. 2. Revise the ventilation calculations using the appropriate room types as shown in Table 403.3, IMC 2000. 3. Confirm the final amount of outside airflow for each fan coil and AC-5 using the procedure shown in Section 403.3.2, IMC 2000. |
| 12/01/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/08/2004 | EGRANT1 | WWM | REVIEW | Needs Review |