Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05176
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
11/29/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a riser diagram for the water piping. 2. Revise the gas piping to conform to the requirements of Table 12-3, 1994 UPC. 3. Provide statement declaring that the intended use of the 3-compartment sink will not result in a grease interceptor being required. |
11/29/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/29/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/29/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
11/29/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the make up air is to be tempered. Reference Section 508.1, IMC 2000. |
11/29/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
12/02/2004 | DROBEY1 | WWM | REVIEW | Completed | |
12/02/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied |