Permit Number: T04CM05176
Parcel: 133231390

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05176
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2004 JIM EGAN FIRE REVIEW Approved
11/29/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the water piping.
2. Revise the gas piping to conform to the requirements of Table 12-3, 1994 UPC.
3. Provide statement declaring that the intended use of the 3-compartment sink will not result in a grease interceptor being required.
11/29/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2004 ROBERT SHERRY WATER REVIEW Approved
11/29/2004 DAN CASTRO ZONING REVIEW Approved
11/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the make up air is to be tempered. Reference Section 508.1, IMC 2000.
11/29/2004 JIM TATE ENGINEERING REVIEW Approved
12/02/2004 DROBEY1 WWM REVIEW Completed
12/02/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied