Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2005 DROBEY1 WWM REVIEW Needs Review
11/29/2004 JIM EGAN FIRE REVIEW Approved
11/29/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/29/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
11/29/2004 ROBERT SHERRY WATER REVIEW Approved
11/29/2004 DAN CASTRO ZONING REVIEW Approved
11/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the ventilation to the space complies with the requirements of Section 403.3, IMC 2000.
2. Show how the existing HVAC system is being modified.
11/29/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2004 JIM TATE ENGINEERING REVIEW Approved