Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05173
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2004 | ANY | ENGINEERING | REVIEW | Approved | |
| 11/26/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The size of the water piping to the urinal in room 105 does not match with the provided specifications. 2. Specify the material used for undergraound water piping. 3. Revise the specified hot water pipe insulation to conformto the requirements of Section 804.5, IECC 2000. |
| 11/26/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/26/2004 | ROBERT SHERRY | WATER | REVIEW | Denied | State whether Tucson Water will be requiring a reduced pressure backflow preventer for this project. |
| 11/26/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the mechanical exhaust for the toilet rooms. Reference Table 403.3 footnote b, UPC 1994. |
| 11/29/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/29/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/17/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/17/2004 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |