Permit Number - T04CM05123
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include all of the fixtures (i.e. the water closet) in the fixture unit calculations. 2. Revise the fixture units for the clothes washer to comply with Table 6-3, UPC 1994. 3. Revise the water pipe sizes to correspond to the submitted calculations. |
| 11/22/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/22/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/22/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 11/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/22/2004 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/22/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 11/24/2004 | LLESNY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/24/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |