Review Details: COMMERCIAL TI

Permit Number - T04CM05107
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
11/18/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
11/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05107 DENIED 11/19/04
1. Account for load on panel schedule, Ckt BB-15. Powers luminaires on Lighting Floor Plan.
2. Clarify amount of lights on tracks. For fixtures B, if one considers the 6 tracks, then (56) (6) = 336 total. This has been added to the fees. Remarks call for a total of 60 lights. If this is the case, each track lighting circuit would have 3000 VA.
3. In the load calculations, Panel B has been added to the load of Panel D. On the Line Diagram, Panel D does not feed Panel B.
4. On the service load calculations, it appears that only one of the chillers is counted. Please correct, or clarify if both may not be operated at the same time.
11/19/2004 JIM EGAN FIRE REVIEW Approved
11/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/22/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY RESTROOM MEET ANSI 117.1 STANDARDS SHOW FIXTURE CLEARANCE ENVELOPES AND TURNING RADIUS.
2) SHOW OR NOTE THAT SITE MEETS ACCESSIBILITY REQUIREMENTS CHAPT. 11.
11/22/2004 ROBERT SHERRY WATER REVIEW Approved
11/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/24/2004 EGRANT1 WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2004 BETH GRANT OUT TO CUSTOMER Completed