Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05107
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 11/18/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM05107 DENIED 11/19/04 1. Account for load on panel schedule, Ckt BB-15. Powers luminaires on Lighting Floor Plan. 2. Clarify amount of lights on tracks. For fixtures B, if one considers the 6 tracks, then (56) (6) = 336 total. This has been added to the fees. Remarks call for a total of 60 lights. If this is the case, each track lighting circuit would have 3000 VA. 3. In the load calculations, Panel B has been added to the load of Panel D. On the Line Diagram, Panel D does not feed Panel B. 4. On the service load calculations, it appears that only one of the chillers is counted. Please correct, or clarify if both may not be operated at the same time. |
| 11/19/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/22/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY RESTROOM MEET ANSI 117.1 STANDARDS SHOW FIXTURE CLEARANCE ENVELOPES AND TURNING RADIUS. 2) SHOW OR NOTE THAT SITE MEETS ACCESSIBILITY REQUIREMENTS CHAPT. 11. |
| 11/22/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/24/2004 | EGRANT1 | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/24/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |