Permit Number: T04CM05068
Parcel: 11517037A

Review Status: Completed

Review Details: SITE

Permit Number - T04CM05068
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2005 JIM EGAN FIRE REVIEW Denied 1. Fire sprinklers required per 2003 IBC Sec. 903.2.7.
2. Minimum one-hour rated fire partitions required for dwelling unit separations per 2003 IBC Sec. 708.
01/06/2005 ANDREW CONNOR NPPO REVIEW Denied Submit NPPO plan or Application for Exception per DS 2-15.0
01/06/2005 Andrew Connor LANDSCAPE REVIEW Denied 1. Submit a separate landscape plan per DS 2-07.0 including the following information:

2. A 10' interior landscape border is required along site boundaries of the adjacent residential properties per LUC Table 3.7.2-I

3. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border per LUC 3.7.2.4. Additional trees are required within the street and interior landscape borders.

4. Fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. LUC 3.7.2.4.A.4

5. 20% of shrubs in landscape border are required to be 5 gallon size DS 2-06.3.5.F

6. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g

7. A 5' wall to screen parking lot from adjacent residential zoned properties is required per LUC Table 3.7.2-I

8. Within a vehicular use area, one (1) canopy tree is required for each (10) motor vehicle parking spaces and canopy trees must be evenly distributed throughout the vehicular use area. Every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a

9. Landscaping along parking lots where plants are susceptible to injury by vehicular traffic must be protected by appropriate means, such as curbs, bollards, or low walls per LUC 3.7.2.3.B.

10. Provide a 30" continuous screen for parking lot along Riverview Blvd. per LUC Table 3.7.2-1

11. The screening requirement is in addition to the landscape requirements. The use of vegetation to satisfy the screen requirement is allowed only to provide for alternative treatment and is not in any way meant to imply that the vegetative screen can also be used to meet the landscape requirement per DS 2-06.3.7

12. Screens may be located in the landscape border if the criteria indicated in LUC3.7.3.2 are met. Vegetative screens shall not extend more than three (3) feet into the street landscape border.


13. Add note to plan: All disturbed areas shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7

14. Landscape plan shall include irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B locations of valves, low-flow bubblers or drip irrigation. Landscape plans are to be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes per LUC 3.7.4.3.B

15. Show the location of refuse storage and a 6' screen is required for adjacent residential properties per LUC Table 3.7.2-I

16. Submit NPPO plan or Application for Exception per DS 2-15.0
01/25/2005 PETER MCLAUGHLIN ZONING HC SITE REVIEW Passed
01/25/2005 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Luis Martinez
1901 N. Dragoon
Tucson, AZ 85745


FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
T04CM05068
Martinez Triplex
1710 W. Riverview Blvd.

TRANSMITTAL: January 25, 2005

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This project is a new use being reviewed for full code compliance.

2. Specify the maximum building height above design grade elevation rather than finished floor elevation along each building wall. To adjacent R-2 zoned property the required perimeter yard building setback is the greater of 10 feet and ¾ height. The minimum setback requirement is not met along the east and west lot lines (7.33 feet proposed). Revise drawing to meet code or a Lot Development Option (LDO) will be required. If an LDO is sought, make all other necessary corrections per these comments, and then bring the plan to the zoning review counter to obtain written comments to be placed on the plan.
LUC 3.2.6.4
DS 2-02.2.1.A.6

3. Concrete wheel stop curbs must be placed in parking spaces where the vehicle overhang may reduce the sidewalk width to less than 4 feet (or in any parking spaces adjacent to sidewalks of less than 6-1/2 feet in width). The drawing indicates a 5-foot width of sidewalk (typical). Revise plan to show the wheel stops in the required parking spaces dimensioned at 2-½ feet from the front of the spaces. DS 3-05.2.3.C

4. Add a general site plan note stating that the development designator is "K" and that the proposed residential development is subject to LUC 3.5.7.1.F. LUC 2.3.5.2.A.2

5. Label and dimension any existing or proposed easements and add their recordation information to the site plan. DS 2-02.2.1.A.20

6. If applicable, the location, type, size and height of any proposed free-standing signage and lighting must be shown. DS 2-02.2.1.A.13 & 25

7. Add a general note to the plan stating the existing use (i.e. vacant).
DS 2-02.2.1.A.31

8. Add a lot coverage calculation to the plan. The lot coverage calc shall also include square footage of vehicle use area. Max allowed coverage per development designator "K" is 75%.
LUC 3.2.3.1.C
LUC 3.2.9
DS 2-02.2.2.A.3

9. Please add a density calculation showing the number of units per acre proposed. With a total of 3 units proposed on a 10,087 square foot (0.23 acre) site the density would be calculated as follows: 3 units ¸ 0.36 acres = 13.4 units per acre proposed. The maximum residential density allowed in the R-2 zone, per development designator "K", is 15 units per acre (proposed density OK).
LUC 3.2.10
LUC 3.2.3.1.C

10. Label centerline and add dimensions to curb and sidewalk along Riverside Blvd. Dimension the ½ right-of way and add sight visibility triangles at the entrance drive along Riverview Blvd.
DS 2-02.2.1.A.10, .19 & .21
DS 3-01.5

11. Accessible pedestrian circulation must provide a connection to the adjacent right-of-way along Riverview Blvd per DS 2-08. The pedestrian circulation system may not cross over the required backup spur. Revise to provide a continuous 4-foot sidewalk, which is physically separated from vehicle use area.
DS 2-08.3.1
DS 2-08.4.1.A
DS 2-02.2.1.A.6

12. Dimension the proposed structures on the drawing. DS 2-05.2.1.A.6

13. Revise the parking calculation to indicate specifically the number of vehicle parking spaces both required and provided. Add a statement on the site plan (sheet a1) that each unit has two bedrooms. DS 2-02.2.2.A.4


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
01/31/2005 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Drainage Statement/Floodplain Use Permit review
DATE: 31 January 2005
ACTIVITY NUMBERS: T04CM05068/T04OT025250
T14S, R13E, Section 3

Engineering Division has reviewed the Subject items, and approval is not recommended at this time. Please provide a Hydrology Report addressing the comments provided below at a minimum, and include a response letter addressing all comments.

*** In accordance with Tucson Code, Section 26-11.2 (i), a review fee of $150.00 will be required prior to resubmittal***

Drainage Statement/Floodplain Use Permit comments:
Refer to Development Standard (DS) 10-02.0 (City of Tucson's Standards Manual for Drainage Design and Floodplain Management), Section 2.3, 5.2 and Tucson Code, Sections 26-5.2 and 26-11-Floodway Fringe and Floodplain permitting requirements, respectively.
1. Include the name, address and telephone number of the project owner and client for whom the report was prepared, if different (DS 10-02.0, Sec. 2.3.1.1 B, C).
2. Provide a table of contents - numbered sequentially, with reference to any appendices (DS 10-02.0, Sec. 2.3.1.1 G
3. The report must address the size, location and hydrologic characteristics of the upstream watershed which affects the site, in accordance with DS 10-02.0, Section 2.3.1.3 A 2).
4. Specify elevation data in the report exhibit for flood depths and the proposed structure's floor elevation to be in accordance with Federal Emergency Management (FEMA) floodplain development requirements. Elevation data must be in accordance with National Geodetic Vertical Datum (NGVD) 1929 for FEMA floodplain development and permitting requirements. Provide North American Vertical Datum (NAVD) 1988 - or a conversion for such from NGVD 29 - as will be necessary for site/grading plan approval. The site plan must include a local benchmark elevation with reference to City datum (NAVD 1988), and reference City Field Book and Page or GPS control point - this information may be available at: http://tdotmaps.transview.org/mapguide_mwf_tdot.htm (DS 2-02.2.1 A 23).
5. Depict 100-year floodplain limits and areas of sheet flooding resulting from 100-year flood peaks of 100-cfs or greater on a site plan contained within the report (El Rio Wash - a federally mapped floodplain). Include spot- or water surface elevations, ground contours, and clearly label the regulatory floodplain as such on the site, grading or drainage plan (DS 10-02 - Sections 2.3.1.4 C 1- 6 & Sec. 5.2.1, 5.2.4 & 5.2.5).
6. Provide an encroachment analysis demonstrating no adverse impact will occur to adjacent properties - upstream or downstream or in the public right of way, and that there will not be an increase in the Base Flood Elevation by more than .1' (Tucson Code, Section 26-.5.2).
7. The report must provide erosion protection and lowest floor elevation recommendations based upon El Rio Wash 100-year flooding depths and velocities (Tucson Code, Sec. 26-5.2
SITE PLAN:
1. Depict 100-year floodplain limits and water surface elevations onsite (DS 2-02.2.1 A 15).
2. Depict drainage patterns, proposed finish floor elevation and finish grades (DS2-02.2.1 A 16)
3. Provide estimated cut and fill quantities DS 2-02.2.1 A 17).
4. Depict existing topographic contours and provide a benchmark based on City of Tucson Datum, including city field book and page number (DS 2-02.2.1 A 23).
5. Demonstrate water harvesting maximization onsite, in accordance with the City of Tucson's Land Use Code (LUC) Section 3.7.1.
6. Depict and label a concrete Driveway apron at the property entrance, to be constructed per Pima County/City of Tucson Standard Detail 206.
7. Depict, label and dimension new 5' sidewalk, 2' from back of curb, to be constructed in the Riverview Bl. right-of-way (DS 3-01.3.3 A, B).
Resubmittal will require a complete hydrology report and a revised site plan addressing all items listed above. Subsequent comments may be necessary upon resubmittal depending on the nature and extent of revisions that occur to the report and/or exhibits.
In accordance with Tucson Code, Section 26-11.2 (i), a review fee of $150.00 will be required prior to resubmittal.
If you have any questions, I can be reached at 791-5550, extension 1189 or Doug.williams@tucsonaz.gov

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2005 TAMI ACHONG OUT TO CUSTOMER Completed
02/10/2005 ANGIE SHOFFSTALL REJECT SHELF Completed