Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM05052
Parcel: 11007414B

Address:
3981 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05052
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2004 JIM TATE ENGINEERING REVIEW Approved
11/17/2004 DAN CASTRO ZONING REVIEW Approved
11/18/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the waste and vent piping for sink P-4 on the waste & vent riser diagram.
2. Revise the size of the reduced pressure backflow preventer to comply with Section 610.2, UPC 1994.
3. If the water heater is not supplied with integral heat traps, provide heat traps for the water heater. Reference Section 804.4, IECC 2000.
4. If the water heater is not supplied with integral heat traps, provide insulation on the first 8 feet of HW and CW piping at the water heater. Reference Section 804.5, IECC 2000.
5. Provide temperature controls for the hot water to comply with Section 804.3, IECC 2000.
11/18/2004 ROBERT SHERRY WATER REVIEW Approved
11/18/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM05052 DENIED 11/18/04
1. Water Heater is 240/3/60 on Sheet P2. Has 208/1/60 on electrical drawings. Pls coordinate with Mechanical and clarify.
2. Fault current uses single 1-500 KCMIL. Line Diagram specifies (4) sets of 750 MCM Aluminum. Please clarify.
11/30/2004 LLESNY1 WWM REVIEW Needs Review
11/30/2004 JIM EGAN FIRE REVIEW Approved
11/30/2004 ANY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2004 LISA LESNY OUT TO CUSTOMER Completed