Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05052
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/17/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
11/17/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
11/18/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the waste and vent piping for sink P-4 on the waste & vent riser diagram. 2. Revise the size of the reduced pressure backflow preventer to comply with Section 610.2, UPC 1994. 3. If the water heater is not supplied with integral heat traps, provide heat traps for the water heater. Reference Section 804.4, IECC 2000. 4. If the water heater is not supplied with integral heat traps, provide insulation on the first 8 feet of HW and CW piping at the water heater. Reference Section 804.5, IECC 2000. 5. Provide temperature controls for the hot water to comply with Section 804.3, IECC 2000. |
11/18/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/18/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM05052 DENIED 11/18/04 1. Water Heater is 240/3/60 on Sheet P2. Has 208/1/60 on electrical drawings. Pls coordinate with Mechanical and clarify. 2. Fault current uses single 1-500 KCMIL. Line Diagram specifies (4) sets of 750 MCM Aluminum. Please clarify. |
11/30/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
11/30/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
11/30/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/30/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |