Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM05031
Parcel: 11005557A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05031
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
11/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/17/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY ANSI 117.1 ACCESS TO RESTROOM FACILITY 113.
2) SHOW WATER CLOSET AND LAVATORY CLEARANCE IN EACH RESTROOM FACILITY.
3) DEMISING PARTITION EXISTING OR NEW?
4) IT APPEARS THE CODE ANALYSIS IS INACCURATE FOR THIS SHELL BUILDING.
11/17/2004 ROBERT SHERRY WATER REVIEW Approved
11/17/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
11/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/17/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t04cm05031 denied 11/17/04

1. Provide size for circuit breaker on PP-33,35.
2. Sheet M1 calls for single phase power for AC-1 and AC-2. Electrical plans call for 3-phase power. Coordinate with Mechanical and clarify.
11/17/2004 JIM EGAN FIRE REVIEW Denied 1. Structure cannot be built over existing property line.
2. Show location of existing 2 hour separation walls at property lines.
12/02/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2004 TAMI ACHONG OUT TO CUSTOMER Completed