Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/23/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TO4CM04995 DENIED 11/18/04 1. Minimum font size 10 point, global, typical. 2. Overall load calculations appear to be accurate, but there are certain internal inconsistencies. For example, Ckt PA-28,30 has the wrong load figures on the Panel Schedule, which effects Ckt L-37,39,41. Lighting on Panel L load calculations is listed at 1200 VA, which I count as 17232. it is up to the discretion of the Engineer to make such internal corrections. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/13/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |