Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM04995
Parcel: 130140260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TO4CM04995 DENIED 11/18/04
1. Minimum font size 10 point, global, typical.
2. Overall load calculations appear to be accurate, but there are certain internal inconsistencies. For example, Ckt PA-28,30 has the wrong load figures on the Panel Schedule, which effects Ckt L-37,39,41. Lighting on Panel L load calculations is listed at 1200 VA, which I count as 17232. it is up to the discretion of the Engineer to make such internal corrections.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2004 TAMI ACHONG OUT TO CUSTOMER Completed