Permit Number: T04CM04995
Parcel: 130140260

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04995
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2004 JIM EGAN FIRE REVIEW Approved
11/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/12/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04995 DENIED 11/12/04
1. Minimum font size is 10 point. Will review specifications on next review.
2. Ckt PA-28,30 powers an outlet in the CERT.ZONE. No load of such on panel schedule.
3. Panel Schedule for L has incorrect load for Panel PA. Ckt L-37,39,41.
4. Load Calculations for Panel PA-1 add existing load. Since this is a new panel, it can not have existing load. Pls clarify.
5. All panels appear overloaded on Load Calculations. All panels have lighting at 1200VA on Load Calculations. PLS check all Load Calculations.
6. 1200A SES appears overloaded, according to Load Calculations, at over 2000A.
11/12/2004 ROBERT SHERRY WATER REVIEW Approved
11/12/2004 DAN CASTRO ZONING REVIEW Approved
11/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/12/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/18/2004 GERRY KOZIOL WWM REVIEW Passed
11/18/2004 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2004 LISA LESNY OUT TO CUSTOMER Completed