Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T04CM04917
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/03/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Provide correct construction type on Sht. G-1 "General Building Summary". (Type 2A or Type 5A?) 2. Type 5A construction not permitted for I-2 Occupancies more that one-story height. 3. Fire hydrants required. Submit approved COT Water Plan. 4. Minimum 20 feet wide fire access roadway required. Minimum required gate width opening is 20 feet. 5. Fire lane signs required. |
| 06/02/2005 | EGRANT1 | ZONING | REVIEW | Needs Review | |
| 06/02/2005 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 06/02/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Needs Review |