Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM04917
Parcel: 115180050

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM04917
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2005 ROBERT SHERRY WATER REVIEW Approved
05/03/2005 JIM EGAN FIRE REVIEW Denied 1. Provide correct construction type on Sht. G-1 "General Building Summary". (Type 2A or Type 5A?)
2. Type 5A construction not permitted for I-2 Occupancies more that one-story height.
3. Fire hydrants required. Submit approved COT Water Plan.
4. Minimum 20 feet wide fire access roadway required. Minimum required gate width opening is 20 feet.
5. Fire lane signs required.
06/02/2005 EGRANT1 ZONING REVIEW Needs Review
06/02/2005 EGRANT1 WWM REVIEW Needs Review
06/02/2005 PATRICIA GILBERT ENGINEERING REVIEW Needs Review