2050 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04CM04899
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2005 PETER MCLAUGHLIN ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Metro Permit Express
1001 N. Alvernon Way #105
Tucson, AZ 85712
(520) 977-7187

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04CM04899
La Paloma Charter School
2050 N. Wilmot Road
Site Plan Review

TRANSMITTAL: January 10, 2005

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

CODE SECTION/
DEVELOPMENT
STANDARD

1. It is acknowledged in response comment #2 that a tentative and a final plat will be submitted. The site plan will approved upon approval of the plat. Or, in order to approve the site plan for the charter school prior to plat approval, the new proposed interior lot line must be removed from the drawing and entire site area must be included for in all calculations. The easement may then be recorded as part of the platting process.

2. The sidewalk providing access to the site from Wilmot Road must be surfaced with Portland cement, brick pavers or any surface equivalent in smoothness, hardness and durability per DS 2-08.5.1.C. Asphaltic concrete may not be used. Revise plan.

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
01/10/2005 PETER MCLAUGHLIN ZONING HC SITE REVIEW Approved
01/13/2005 Loren Makus ENGINEERING REVIEW Denied DATE: January 14, 2005
TO: Douglas Seaver, Architect.
SUBJECT: La Paloma Charter School, 2050 N. Wilmot Rd. Site Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBERS: T04CM04899

SUMMARY: The Site Plan was reviewed by Development Services Department Engineering Division and was not approved at this time. Revise the site plan in accordance with the following comments..
Site Plan comments:
1. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. See comment No. 2 of the DR.
2. Provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
3. 10. List estimated cut & fill quantities per D.S. 2-02.2.1.17.
4. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP.
5. Provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
6. Provide all drainage details on the Site Plan.
7. The Stormwater Pollution Prevention Plan will be reviewed with the grading plan.
8. Revise the entry sidewalk on the Site Plan to provide a concrete surface or the equivalent as required by the Development Standard 2-08.5.1.C.

Revise the Site Plan, to address all of these comments and resubmit two copies of the Site Plan and Drainage Report. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
12/16/2004 Jim Egan FIRE REVIEW Approv-Cond Site is conditionally approved. Building permit plans will not be approved until an approved COT Water Plan is included with the permit plans.
12/20/2004 Andrew Connor LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2005 BETH GRANT OUT TO CUSTOMER Completed
01/18/2005 SUE REEVES REJECT SHELF Completed