Permit Number: T04CM04888
Parcel: 11004345J

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T04CM04888
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04888 DENIED 12/15/04
1. Revisions to approved plans shall be made on full sized sheets.
2. Revisions to approved plans shall be sealed by the Registrant.
· Arizona Revised Statutes § 32-125 (B) and (E)
· Arizona Administrative Code, Title 4, Chapter 30, R4-30-304
3. For all branch circuits that have different panel/circuit # from those of the approved plans, Electrical Plan shall be revised as well.
12/16/2004 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review