Permit Number: T04CM04888
Parcel: 11004345J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04888
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2004 JIM EGAN FIRE REVIEW Approved
11/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water fixture units for the clothes washer. Reference Table 6-3 (Public), UPC 1994.
2. Resize the DCW supply to the water heater and to the clothes washer to coordinate with the submitted calculations.
3. Clarify how the standpipe for the clothes washer is to be wet vented with the mop sink.
11/08/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY SITE AND RESTROOM MEETS CHAPT 11 ACCESSIBILITY REQUIREMENTS AND ANSI STANDARDS A117.1.
OR JUSTIFY WITH BID NUMBERS PER CHAPT 34 THAT 20% COST OF CONSTRUCTION IS BEING SPENT ON MEETING CHAPT. 11 REQUIREMENTS.
2) CLARIFY CHAPT. 16 SECTION 1621.1.2 LATERAL BRACING FOR PARTITIONS.
3)PROVIDE CODE ANALYSIS SHEET AVAILABLE ON CITY OF TUCSON WEBSITE.
11/08/2004 ROBERT SHERRY WATER REVIEW Approved
11/08/2004 DAN CASTRO ZONING REVIEW Approved
11/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations to comply with Sections 403.3 and 403.3.2, IMC 2000.
11/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04888 DENIED 11/08/04

1. Complete lighting Fixture Schedule.
2. Existing circuit loads shall be counted with panel load calculations.
3. A119-8 has receptacle load on Power Plan, but none allocated on panel schedule. Pls clarify.
4. Heating Unit 6, on Ckt A119B-1,3, would have 20900 VA. This computes to over 100A. Does not appear that the 50 A Ckt is adequate. Pls clarify.
5. Heating Unit 8, on A119-16,18, only has load on panel schedule on 18. Panel schedule is not set up to document both sides of panel.
6. Same as Comment #5 above for Heating Unit 9.
7. Same as Comment #5 above for Dryer.
8. Check remaining circuits per Comments 5, 6, and 7 above.
9. Provide service load calculations.
11/08/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/12/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed