01/03/2005 ROBERT SHERRY WATER REVIEW Approved
01/04/2005 Jim Egan FIRE REVIEW Denied 1. Inadequate exterior openings provided for 1st floor enclosed parking garage per 2003 IBC Sec. 903.2.10.
2. Class 1 manual dry standpipe outlets shall be located in accordance with 2003 IBC Sec. 905.3.1 Exception 3.
3. Doors in 2 hour rated fire barriers shall be protected in accordance with 2003 IBC Sec. 715 and Table 715.3.
(Door #s 101F, 101G, 105G, 105H, 108 and 109)
01/05/2005 MATT FLICK ENGINEERING REVIEW Approved Conforms to approved site and grading plans.
01/05/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
01/06/2005 GERRY KOZIOL WWM REVIEW Denied cannot drain elevator sump pump to mop sink shown on drawing P3.1- Per WW/8th floor /IRD.