| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/04/2005 | Jim Egan | FIRE | REVIEW | Denied | 1. Inadequate exterior openings provided for 1st floor enclosed parking garage per 2003 IBC Sec. 903.2.10. 2. Class 1 manual dry standpipe outlets shall be located in accordance with 2003 IBC Sec. 905.3.1 Exception 3. 3. Doors in 2 hour rated fire barriers shall be protected in accordance with 2003 IBC Sec. 715 and Table 715.3. (Door #s 101F, 101G, 105G, 105H, 108 and 109) |
| 01/05/2005 | MATT FLICK | ENGINEERING | REVIEW | Approved | Conforms to approved site and grading plans. |
| 01/05/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 01/06/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | cannot drain elevator sump pump to mop sink shown on drawing P3.1- Per WW/8th floor /IRD. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/06/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 01/06/2005 | SUE REEVES | REJECT SHELF | Completed |