Permit Number: T04CM04874
Parcel: 129020300

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04874
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM04874

3/10/05 548 S. COUNTRY CLUB RD.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.




STRUCTURAL PLANS:

1. DETAIL THE GABLE END BRACING.

2. DETAIL HOW THE SHEAR IN TRANSFERRED FROM THE WALL TO THE ROOF DECK.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY. I CAN'T FIND IT ON THE ROOF PLAN AS STATED.

2. HOW IS THE STUCCO FOAM SHIELDED IN THE ATTIC FROM IGNITION. SEE R318.2.3 .

PLUMBING PLANS:

1. THE FIXTURE DEMANDS AREN'T PER THE UPC. THE WRONG TABLE IS CITED. PLEASE SEE THE UNIFORM PLUMBING CODE'S TABLE 6-3 FOR THE FIXTURE UNITS. TABLE 6-4 IS THE TABLE TO SIZE THE WATER DISTRIBUTION SYSTEM. TABLE 6-5 DOESN'T APPLY.

2. PLEASE CLARIFY/AMEND THE NOTE IN THE GAS LINE THAT MENTIONS "3/4" GAS LINE CONTINUED ON SITE PLAN". IS THIS LINE A 1" OR ¾" LINE?




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
04/25/2005 DELMA ROBEY OUT TO CUSTOMER Completed