Permit Number: T04CM04871
Parcel: 13408276A

Address:
8301 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04871
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2005 DROBEY1 ENGINEERING REVIEW Needs Review
01/27/2005 DROBEY1 WWM REVIEW Needs Review
01/27/2005 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
01/27/2005 DROBEY1 ZONING REVIEW Needs Review
01/27/2005 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/05/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagram of the gas piping system.
2. Revise the sizes of the gas piping to comply with the requirements of Table 12-3, UPC 1994.
11/05/2004 JIM EGAN FIRE REVIEW Approved
11/05/2004 ROBERT SHERRY WATER REVIEW Approved
11/05/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the balancing data and equipment specifications for the new equipment on a drawing sealed by an Arizona Registrant, not on an unsealed reference document.
2. Show the location of the new exhaust fan on the drawing. The minimum separation of the exhaust termination and the intake of the makeup air unit is ten feet.
3. Provide calculations to show that the hood is adequately supported from the structure. Reference Section 507.6, IMC 2000.