Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04871
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/27/2005 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 01/27/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 01/27/2005 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/27/2005 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 01/27/2005 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/05/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagram of the gas piping system. 2. Revise the sizes of the gas piping to comply with the requirements of Table 12-3, UPC 1994. |
| 11/05/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/05/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the balancing data and equipment specifications for the new equipment on a drawing sealed by an Arizona Registrant, not on an unsealed reference document. 2. Show the location of the new exhaust fan on the drawing. The minimum separation of the exhaust termination and the intake of the makeup air unit is ten feet. 3. Provide calculations to show that the hood is adequately supported from the structure. Reference Section 507.6, IMC 2000. |