Permit Number: T04CM04863
Parcel: 124161440

Address:
1134 S PARK AV

Review Status: Completed

Review Details: SITE

Permit Number - T04CM04863
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2004 Jim Egan FIRE REVIEW Approv-Cond Fire approval for site only.
11/19/2004 ANDREW CONNOR NPPO REVIEW Passed
11/19/2004 Andrew Connor LANDSCAPE REVIEW Passed
11/20/2004 PATRICIA GEHLEN ZONING HC SITE REVIEW Passed
11/20/2004 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
11/20/2004
1) Revise % expansion calculation (denominator should be existing GFA only) DS 2-02.2.2.A.6,
2) Add development designator and new FAR to site plan general notes (DS 2-02.2.2.A.3,
3) Provide an elevation which dimensions the height of the addition from design grade (DS 2-02.2.1.A.6),
4) Add the adjacent zoning to the site plan (DS 2-02.2.1.A.28). Since the zoning west of this site is R-2, the setback for the addition 1.5 times the height of the structure. Revise plans as required (LUC 3.2.6.4),
5) If there is outdoor storage on the exterior slab or in the existing yard, please revise parking calculation to include this storage areas (DS 2-02.2.2.A.4),
6) Since the last approved site plan does not include the concrete slab or fenced in yard, please dimension vehicle use area to ensure sufficient on-site manuverability (DS 2-02.2.1.A.8 & 11).
11/30/2004 Loren Makus ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed
12/03/2004 ANGIE SHOFFSTALL REJECT SHELF Completed