Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM04818
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM04818
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2004 JIM EGAN FIRE REVIEW Approved
11/09/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
11/10/2004 ANY ENGINEERING REVIEW Approved
11/10/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
11/16/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11-16-04
ACTIVITY NUMBER: T04CM04818
PROJECT NAME: ROCKIES RAMADA & TOWER
PROJECT ADDRESS: 3400 E. CAMINO CAMPESTRE
ARCHITECT / ENGINEER: KLINDT D. BRECKENRIDGE, WALT ROGERS
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

1) CLARIFY OCCUPANCY GROUP OF CELL PHONE BLDG. - SEE SECTION 704.3 OF THE 2003 IBC. ARCHITECT OF RECORD FOR CODE ANALYSIS SHOULD SEAL AND SIGN DIMENSIONED SITE PLAN.

2) CLARIFY TOP OF ROOF HEIGHTS FOR RAMADA AND TOWER.

3) CLARIFY COLUMN SIZE FOR RAMADA SHT S-2 SPECIFIES A 10" X 10", STRUCTURAL CALCULATIONS SPECIFIES A 7" X7". .

4) SIZE OF FILLET WELD IS NOT SPECIFIED ON SHT. S-2 PLAN VIEW OF COMPRESSION RING.

5) SHT. D7 / S-2 CLARIFY WELD @ MID BEAM CONNECTION DETAIL #1.

6) SHT. D7 / S-2 CLARIFY WELD @ MID BEAM CONNECTION DETAIL # 2.

7) CLARIFY- COLUMN PERSPECTIVE TYPICAL COLUMN AND BEAM CONNECTION SHT. S-2 NOTES 3/8" A325 BOLTS WELDED TO PLATE - STRUCTURAL CLACULATION SHT. D8 SPECIFIES 5/8" BOLTS.

8) CLARIFY- ANCHOR BOLT @ TYPICAL FOOTING DETAIL CALLS OUT A 5/8" X 12" A307 WITH 10" MIN. EMBED - D9 STRCUTURAL CALCULATIONS SPECIFIES 5/8" X 10" A307 ANCHOR BOLT WITH 8" MIN. EMBED.

9) CLARIFY - DRAWING S-1 COMPRESSION RING SPECIFIES A 5"X5" MAIN BEAM AND 4 X 4 MAIN BEAM.

10) S-1 COMPRESSION RING - CLARIFY FILLET WELD @ ENDPLATE TO COMPRESSION RING PER STRUCTURAL CALCULATIONS SHT 45.

11) CLARIFY - DRAWING S-1 PERIMETER BEAM TO BEAM SECTION SPECIFIES A 4" X 4" BEAM, SHT. 67 STRUCTURAL CALCULATIONS SPECIFIES A 4 X 4 BEAM, SHT. S-1 PLAN VIEW SPECIFIES A 6 X 6 BEAM.

12) SHT. S-1 CONNECTION @ 6" X 6" BOX CLOCK FRAME TO 5" X 5" CONNECTOR BEAM SPECIFIES A 3/16" WELD - PLEASE JUSTIFY.

13) SHT. S-1 TYPICAL FOOTING DETAIL SPECIFY FILLET WELD PER STRUCTURAL CALCULATIONS SHT 50.

14) CLARIFY - D8 STRUCTURAL CALCULATIONS SPECIFIES 5/8" X 10" ANCHOR BOLT, DRAWING S-1 SPECIFIES 5/8" X 12" .

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2004 TAMI ACHONG OUT TO CUSTOMER Completed
11/17/2004 SUE REEVES REJECT SHELF Completed