Permit Number - T04CM04804
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2005 Jim Egan FIRE REVIEW Approved
01/10/2005 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Second request. The design appears violate the listing of the equipment, which requires 66" of clearance below the tube. Revise the installation of the radiant heaters to provide the manufacturer's required clearances. Reference Section 304.1, IMC 2000.
2. Coordinate the marks for the radiant heaters and the thermostats.
01/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Recreation = class B pool, Pool code sec 719.(a) There shall be separation between the spaces used by visitors and spectators in street clothes and those spaces used by users. The visitor and spectator area may be within the pool perimeter enclosure if it is in a separate area segregated from the space used by users. Clarify which fence shall be considered pool enclosure. All gates must be equipped with self-closing and positive self-latching closure @ min. 45" A.F.F. and a min. 5 ft high per amendments code section 3109.
2) Separate toilet facilities shall be provided for spectators. ANSI/NSPI-1 1991 Artcile XVIII section 18.1 and 18.2. Justify recreation has enough facilities to carry additional occupant load. Clarify distance traveled.

3) Clarify on floor plans accessibility ANSI A117.1 clear floor space requirements have been met for restroom facility. Section 606.6 exposed pipes and surfaces (under lavatory), please clarify.

4) ANSI/NSPI -1 1991 Section 17.4 Shower and dressing booths shall be provided in female dressing space. Dressing booths shall be provided with curtains or other means of seclusion.

5) Pool stair handrail not shown on sht. A101 please clarify.

6) Detail 2/SP3.3 clarify dimensions per ANSI 5.5, recessed treads min. depth of 5" & minimum width of 12".

7) Light Pole base structural calcuations and specifications. Documents/copies are not readable. Please provide a clear copy.
01/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The floor sinks for the pool equipment room and the floor drain for the ozone room appear to be acting as indirect wastes. Provide traps and vents per Section 803.0, UPC 1994. If the traps will be infrequently used, Provide trap seal protection. Reference Section 1007.1, UPC 1994 as amended by the State of Arizona.
01/21/2005 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
01/23/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
01/24/2005 Gerry Koziol WWM REVIEW Approved
01/28/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond ACTIVITY NUMBERS: T04BU02737
ASSOCIATED NUMBERS: T04CM04804, & T04BU02662
LOCATION: T14S, R14E, Section 19
SUBJECT: COT Parks & Recreation Quince Douglas Pool Facility Resubmittal for the Grading Plan /SWPPP Engineering Review
REVIEWER: Elizabeth Eberbach

SUMMARY: DSD Engineering Division has reviewed the plan set re-submittal for Grading Plan and SWPPP review. DSD Engineering recommends CONDITIONAL APPROVAL (with conditions for the civil drawings C1 - C5 and the SWPPP report), AT TIME OF HEALTH DEPARTMENT APPROVAL. The Drainage Report was accepted for this project only.

GRADING PLAN /SWPPP CONDITIONS OF APPROVAL:
1) HEALTH DEPARTMENT APPROVAL required prior to approval and issuance of permits.
2) Estimate for total disturbance area is labeled as 227,745 square feet as noted on sheet C2.
3) REGARDING SHEET C1, SEE Survey Field Book 1989-A-1 Page 70 FOR BENCHMARK REFERENCE.
4) GRADE TO DRAIN AWAY FROM STRUCTURES.
5) The signatures from the operators must be on the SWPPP on the site copy of the SWPPP at or before the commencement of construction.
6) Contractor must complete the Notice of Intent and submit it to ADEQ and the City of Tucson 48 hours prior to commencement of construction activity.
7) Clearing and grubbing and demolition will occur after the erosion controls are established. CALL FOR DSD INSPECTION / PRE-CON AT TIME OF INTERIM EROSION CONTROL INSTALLATION.

If you have any questions, call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2005 BETH GRANT OUT TO CUSTOMER Completed
02/04/2005 BETH GRANT REJECT SHELF Completed