01/10/2005 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1/14/05
ACTIVITY NUMBER: T04CM04796
PROJECT NAME: Storage Racks
PROJECT ADDRESS: 2020 W. Prince Rd.
ARCHITECT / ENGINEER:
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Structural Calculations should be based on 2003 IBC equations as specified. It appears the equations reference the 2000 IBC.
2) Clarify that signage will be posted clarifying allowable loads per type of storage rack.
12/27/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved OLD FUP #627

T04OT02256

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/18/2005 ANGIE SHOFFSTALL REJECT SHELF Completed