Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04795
Parcel: 133452200

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04795
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The retail occupancy category provides ventilation to offset the contaminants associated with stock merchandise, not people. A more appropriate category for the "Open Office" area (room 102) is Hotel Lobby, with an occupant load of 30 people per 1000 square feet and 15 CFM of outside air per person. Revise the submitted ventilation calculations in accordance with Sections 403.3 and 403.3.2, IMC 2000.
03/10/2005 GERRY KOZIOL WWM REVIEW Denied need to review location/method of connection to public sewer. 6" connection to manhole requires a manhole tap permit.waste water maps & records 5th floor. 740-6606
03/25/2005 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
3/25/2005
The GFA on the building plans is larger than that shown on the approved development plan. Revise one or the other for consistency.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2005 TAMI ACHONG OUT TO CUSTOMER Completed
03/29/2005 SUE REEVES REJECT SHELF Completed