Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04795
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/08/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The retail occupancy category provides ventilation to offset the contaminants associated with stock merchandise, not people. A more appropriate category for the "Open Office" area (room 102) is Hotel Lobby, with an occupant load of 30 people per 1000 square feet and 15 CFM of outside air per person. Revise the submitted ventilation calculations in accordance with Sections 403.3 and 403.3.2, IMC 2000. |
| 03/10/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | need to review location/method of connection to public sewer. 6" connection to manhole requires a manhole tap permit.waste water maps & records 5th floor. 740-6606 |
| 03/25/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 3/25/2005 The GFA on the building plans is larger than that shown on the approved development plan. Revise one or the other for consistency. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 03/29/2005 | SUE REEVES | REJECT SHELF | Completed |