Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM04791
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/07/2004 | Bruce Stevens | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS PROJECT #T04CM04791 12/07/2004 5120 E. Circulo de las Cabanas Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: 1. All plans shall be legible and a scale no smaller than ΒΌ inch = 1-foot shall be used for all floor plans, framing plans and elevations. Details and cross sections shall be a minimum 3/8 inch = 1-foot scale. 2. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. FOUNDATION PLANS: 1. All exterior doors require a landing or floor at the exterior. Landings must be at least as wide as the doors they serve and 36" in the direction of travel per R311.4.3. FLOOR PLANS: 1. Show compliance with R310 providing egress from bedrooms to meet the following minimum specifications. - Maximum sill height of 44". - Minimum net clear opening area of 5.7SF. - Minimum net clear opening dimension of 24" height and 20" width. The windows in the master bedroom and bedroom #2 do not appear to comply. STRUCTURAL PLANS: 1. The 4X12 beam specified at the bedroom #3 extension will not support the roof loads imposed. ELEVATIONS: 1. Note and dimension that the fireplace chimney must terminate a minimum of 2' above any point of roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, per R1001.6. PLUMBING PLANS: 1. Note and specify all piping materials. 2. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type. ELECTRICAL PLANS: 1. Show locations of smoke detectors per R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors per R313.1.1. If you have any questions, please contact your assigned plans examiner Bruce Stevens at 791-5550, extension 1174. NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/15/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/15/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |