Permit Number: T04CM04755
Parcel: 13322471B

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04CM04755
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2005 JIM EGAN FIRE REVIEW Denied Fire hydrant(s) required. Submit approved COT Water Plan.
04/06/2005 LOREN MAKUS ENGINEERING REVIEW Approved
04/12/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Identify on site plan the 30"continuous screen wall indicated in Keynote #20 per LUC Table 3.7.2-I

2. Show all existing and proposed screen walls on the landscape identical to the site and grading plans per DS 2-07.2.2.A.3.a

3. Clearly identify on irrigation plan the source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

4. Revise the number or provide the locations of the (214) Prosopis velutina indicated in landscape schedule on Sheet L.1

5. Provide the locations of TOS Prosopis velutina on landscape plan per DS 2-15.3.4.B.2
04/13/2005 ANDREW CONNOR NPPO REVIEW Denied Provide the locations of TOS Prosopis velutina on landscape plan per DS 2-15.3.4.B.2
04/20/2005 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Terry Stevens
Senior Planner

FOR: David Revira
Principal Planner

PROJECT: T04CM04755
New Retail Shell Pad
Site Plan

TRANSMITTAL: 04/20/05 ------ 2nd Review


COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

This site plan has been reviewed for compliance with the site content and specifications of Development Standards 2-02, 2-08, 2-09, 3-01, 3-05. Please address all comments and revise the drawing as required.


1. The previous review requested to resubmit all red line drawings and a response letter. Please comply for the second resubmittal.

2. Portion of previous comment: It does not appear that adequate bicycle parking facilities are provided as indicated on the site plan. Off-street bicycle parking locations (individually} must be drawn specifically on the site plan. Indicate clearly on the site plan the number and type for both buildings. If necessary a detail drawing must be added to the plan, which depicts the location and the type, of all bicycle parking facilities proposed. DS 2-02.2.1.A.9

3. Draw and label future sight visibility triangles as measured from future curb. DS 2-02.2.1.A.10

4. The sidewalks must be accessible routes for the handicapped. Please draw a detail or indicate on the site plan how accessibility is provided for the handicapped from the handicapped parking space aisles to the sidewalks. Access ramp(s) missing at handicapped parking space aisle(s) at the south side of new retail building. See redlines for more information needed on pedestrian circulation, i.e. access ramps, crosswalks.DS 2-02.2.1A.12

5. Portion of previous comment: List subject to section number which applies to this designator. Add subject to section number 3.5.9.2..A List the type existing and proposed of retail uses, i.e. "General Merchandise DD 31", Also please list any subject to section numbers applicable to the proposed and existing uses.

6. Revise the required setback line at the east property line to the required 11/2 times the height of building measured from design grade. Currently indicated as 37.5', required 39'.

If you have any questions about this transmittal, please call Terry Stevens or David Rivera, (520) 791-5608.
04/20/2005 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2005 GBONILL1 OUT TO CUSTOMER Completed