Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04749
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/27/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
10/27/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/27/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/27/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/27/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
10/27/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/27/2004 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
10/29/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/29/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04749 DENIED 10/27/04 1. Distinguish new from existing equipment. 2. Clarify the treatmenrt of continuous loads and largest motor on panel schedule load claculations. If such are added at 1.25%, it appears that the load would be aprox. 89-90 A, not 77A. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/29/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |