Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04749
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04749
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2004 JIM EGAN FIRE REVIEW Approved
10/27/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/27/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/27/2004 ROBERT SHERRY WATER REVIEW Approved
10/27/2004 DAN CASTRO ZONING REVIEW Approved
10/27/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/27/2004 LOREN MAKUS ENGINEERING REVIEW Approved
10/29/2004 GERRY KOZIOL WWM REVIEW Approved
10/29/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04749 DENIED 10/27/04
1. Distinguish new from existing equipment.
2. Clarify the treatmenrt of continuous loads and largest motor on panel schedule load claculations. If such are added at 1.25%, it appears that the load would be aprox. 89-90 A, not 77A.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2004 BETH GRANT OUT TO CUSTOMER Completed