Permit Number: T04CM04746
Parcel: 133180090

Address:
1041 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04746
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/26/2004 PATRICIA GEHLEN ZONING REVIEW Approved
10/27/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/27/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY THAT EXISTING RESTROOM MEETS ANSI STANDARDS A117.1 OR JUSTIFY WITH PROVIDED CONSTRUCTION COSTS THAT REQUIRED AMOUNT IS BEING SPENT TOWARDS ACCESSIBILITY REQUIREMENTS.
10/27/2004 ROBERT SHERRY WATER REVIEW Approved
10/27/2004 JIM EGAN FIRE REVIEW Approved
10/27/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04746 DENIED 10/27/04
1. General Note 8 Sheet CS calls for deferred submittals. Clarify intent. If electrical is to be submitted at a later time, this project will not be considered for permit until such time. If the drawings on this set of plans represent and specify the electrical work, please remove the note.
2. Electrical Plans shall be sealed by an Architect or Engineer registered in the State of Arizona. This is a requirement for any occupancy greater than 20, for work on a building greater than 3000 SF, and for work prepared by a Registrant.
3. Provide lighting schedule and cut sheets for all new fixtures.
4. Identify panel and circuit number for all new electrical loads/devices.
5. Provide panel schedule with load calculations.
6. There is a note on Sheet E1 to the effect that the Contractor shall submit supporting documentation to facilitate permitting. Such documentation shall be added to the plans by the Registrant before consideration for permit.
11/17/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2004 BETH GRANT OUT TO CUSTOMER Completed