Permit Number: T04CM04705
Parcel: 10603167C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04705
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2004 JIM EGAN FIRE REVIEW Approved
10/25/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T04CM04705 .. DGL .. 3550 N 0RACLE RD .. 10/25/04 ..

S1. Clarify accessibility to showers. toilet rooms , regular massage room and wet massage room.
S2. Clarify accessibility to site and buildings per IBC Sec 3408.
S3. Provide details of construction for :
1. Walls , showers, typical partition , wet massage room.
2. Ceilings at showers and wet massage room.
3. Accessibilty.
show materials of construction and connections to structure within , above and below.
S4, Show conformance with Tucson City Code Sec 7-137 , available at City Code Website.
S5. Provide project valuation.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111
10/25/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
10/25/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/29/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A 2" waste line can handle a maximum of 8 fixture units. Revise plans.
2. Based on the supplied calculations, a 1" pipe cannot supply the required 14 water fixture units.
3. Provide waste and vent riser diagram of the new shower installation.
10/29/2004 ROBERT SHERRY WATER REVIEW Approved
10/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2004 GERRY KOZIOL WWM REVIEW Approved